Title 30
SECTION 75.907
75.907 Design of trailing cables for medium-voltage circuits.
§ 75.907 Design of trailing cables for medium-voltage circuits. [Statutory Provisions]Trailing cables for medium-voltage circuits shall include grounding conductors, a ground check conductor, and grounded metallic shields around each power conductor or a ground metallic shield over the assembly, except that on equipment employing cable reels, cables without shields may be used if the insulation is rated 2,000 volts or more.