Appendix D to Part 227 - Audiometric Test Rooms
49:4.1.1.1.21.4.15.1.45 : Appendix D
Appendix D to Part 227 - Audiometric Test Rooms
This appendix is mandatory.
A. Rooms used for audiometric testing shall not have background
sound pressure levels exceeding those in Table D-1 when measured by
equipment conforming at least to the Type 2 requirements of ANSI
S1.4-1983 (Reaffirmed 2001) and to the Class 2 requirements of ANSI
S1.11-2004, “Specification for Octave-Band and
Fractional-Octave-Band Analog and Digital Filters.”
B. The Director of the Federal Register approves the
incorporation by reference of ANSI S1.4-1983 (Reaffirmed 2001) and
S.1.11-2004 in this section in accordance with 5 U.S.C. 552(a) and
1 CFR part 51. You may obtain a copy of the incorporated standard
from the American National Standards Institute at 1819 L Street,
NW., Washington, DC 20036 or http://www.ansi.org. You may
inspect a copy of the incorporated standard at the Federal Railroad
Administration, Docket Room, 1200 New Jersey Avenue, SE.,
Washington, DC 20590, or at the National Archives and Records
Administration (NARA). For information on the availability of this
material at NARA, call 202-741-6030, or go to
http://www.archives.gov/federal_register/code_of_federal_regulations/ibr_locations.html.
Table D-1 - Maximum Allowable Octave-Band
Sound Pressure Levels for Audiometric Test Rooms
Octave-band center frequency
(Hz) |
500 |
1000 |
2000 |
4000 |
8000 |
Sound pressure
levels - supra-aural earphones |
40 |
40 |
47 |
57 |
62 |
Sound pressure
levels - insert earphones |
50 |
47 |
49 |
50 |
56 |
[71 FR 63123, Oct. 27, 2006, as amended at 74 FR 25173, May 27,
2009]