Table 3 to Subpart HHH of Part 62—Operating Parameters To Be Monitored and Minimum Measurement and Recording Frequencies

Operating Parameters To Be Monitored and Minimum Measurement and Recording Frequencies

CorpusDaily eCFR
Displayed edition2026-04-27
Last updated2026-04-27

Table 3 to Subpart HHH of Part 62—Operating Parameters To Be Monitored and Minimum Measurement and Recording Frequencies

Operating

parameters

to be

monitored
Minimum frequencyHMIWI
Data measurementData recordingHMIWI with combustion control onlyHMIWI with dry scrubber followed by FFHMIWI with wet scrubberHMIWI with dry scrubber followed by FF and wet scrubberHMIWI with SNCR system
Maximum operating parameters:
Maximum charge rateOnce per chargeOnce per charge
Maximum FF inlet temperatureContinuousOnce per minute
Maximum flue gas temperatureContinuousOnce per minute
Minimum operating parameters:
Minimum secondary chamber temperatureContinuousOnce per minute
Minimum dioxin/furan sorbent flow rateHourlyOnce per hour
Minimum HCl sorbent flow rateHourlyOnce per hour
Minimum mercury (Hg) sorbent flow rateHourlyOnce per hour
Minimum pressure drop across the wet scrubber or minimum horsepower or amperage to wet scrubberContinuousOnce per minute
Minimum scrubber liquor flow rateContinuousOnce per minute
Minimum scrubber liquor pHContinuousOnce per minute
Minimum reagent flow rateHourlyOnce per hour

[78 FR 28076, May 13, 2013]