Title 30

SECTION 75.601-3

75.601-3 Short circuit protection; dual element fuses; current ratings; maximum values.

§ 75.601-3 Short circuit protection; dual element fuses; current ratings; maximum values.

Dual element fuses having adequate current-interrupting capacity shall meet the requirements for short circuit protection of trailing cables as provided in § 75.601, however, the current ratings of such devices shall not exceed the maximum values specified in this section:

Conductor size (AWG or MGM) Single conductor cable Two conductor cable
Ampacity Max. fuse rating Ampacity Max. fuse rating
14 15 15
12 20 20
10 25 25
8 60 60 50 50
6 85 90 65 70
4 110 110 90 90
3 130 150 105 110
2 150 150 120 125
1 170 175 140 150
1/0 200 200 170 175
2/0 235 250 195 200
3/0 275 300 225 225
4/0 315 350 260 300
250 350 350 285 300
300 395 400 310 350
350 445 450 335 350
400 480 500 360 400
450 515 600 385 400
500 545 600 415 450