Table 3 to Subpart HHHHHHH of Part 63—Summary of Control Requirements for Storage Vessels at New and Existing Sources
| If the storage vessel capacity (gallons) is . . . | And the vapor pressure a (psia) is . . . | Then, you must use the following type of storage vessel . . . |
|---|---|---|
| ≥20,000 but <40,000 | ≥4 | Internal floating roof, external floating roof, or fixed roof vented to a closed vent system and control device achieving 95 percent reduction.b |
| ≥40,000 | ≥0.75 | Internal floating roof, external floating roof, or fixed roof vented to a closed vent system and control device achieving 95 percent reduction.b |
| Any capacity. | >11.1 | Pressure vessel.c |
| All other capacity and vapor pressure combinations | Fixed roof.d | |
| a Maximum true vapor pressure of total HAP at storage temperature. | ||
| b If using a fixed roof storage vessel vented to a closed vent system and control device, you must meet the requirements in § 63.11910(a) for fixed roof storage vessels. If using an internal floating roof storage vessel or external floating roof storage vessels, you must meet the requirements in § 63.11910(b) for internal floating roof storage vessels or external floating roof storage vessels, as applicable. | ||
| c Meeting the requirements of § 63.11910(c) for pressure vessels. | ||
| d Meeting the requirements in § 63.11910(a) for fixed roof storage vessels. |