Table 1 to Subpart III of Part 62—Emission Limitations

Emission Limitations

CorpusDaily eCFR
Displayed edition2026-04-15
Last updated2026-04-15

Table 1 to Subpart III of Part 62—Emission Limitations

For the air pollutantYou must meet this emission limitation aUsing this averaging timeAnd determining compliance using this method
Cadmium0.004 milligrams per dry standard cubic meter3-run average (1 hour minimum sample time per run)Performance test (Method 29 of appendix A of part 60).
Carbon monoxide157 parts per million by dry volume3-run average (1 hour minimum sample time per run)Performance test (Method 10, 10A, or 10B, of appendix A of part 60).
Dioxins/furans (toxic equivalency basis)0.41 nanograms per dry standard cubic meter3-run average (4 hour minimum sample time per run)Performance test (Method 23 of appendix A of part 60).
Hydrogen chloride62 parts per million by dry volume3-run average (1 hour minimum sample time per run)Performance test (Method 26A of appendix A of part 60).
Lead0.04 milligrams per dry standard cubic meter3-run (1 hour minimum sample time per run)Performance test (Method 29 of appendix A of part 60).
Mercury0.47 milligrams per dry standard cubic meter3-run average (1 hour minimum sample time per run)Performance test (Method 29 of appendix A of part 60).
Opacity10 percent6-minute averagesPerformance test (Method 9 of appendix A of part 60).
Oxides of nitrogen388 parts per million by dry volume3-run average (1 hour minimum sample time per run)Performance test (Methods 7, 7A, 7C, 7D, or 7E of appendix A of part 60).
Particulate matter70 milligrams per dry standard cubic meter3-run average (1 hour minimum sample time per run)Performance test (Method 5 or 29 of appendix A of part 60).
Sulfur dioxide20 parts per million by dry volume3-run average (1 hour minimum sample time per run)Performance test (Method 6 or 6c of appendix A of part 60).
a All emission limitations (except for opacity) are measured at 7 percent oxygen, dry basis at standard conditions.