Table 2 to Subpart TTTT of Part 60—CO2 Emission Standards for Affected Stationary Combustion Turbines That Commenced Construction After January 8, 2014, and Reconstruction After June 18, 2014 (Net Energy Output-Based Standards Applicable as Approved by the Administrator)
| Affected EGU | CO2 Emission standard |
|---|---|
| Newly constructed or reconstructed stationary combustion turbine that supplies more than its design efficiency or 50 percent, whichever is less, times its potential electric output as net-electric sales on both a 12-operating month and a 3-year rolling average basis and combusts more than 90% natural gas on a heat input basis on a 12-operating-month rolling average basis | 450 kg CO2/MWh (1,000 lb CO2/MWh) of gross energy output; or 470 kg CO2/MWh (1,030 lb CO2/MWh) of net energy output. |
| Newly constructed or reconstructed stationary combustion turbine that supplies its design efficiency or 50 percent, whichever is less, times its potential electric output or less as net-electric sales on either a 12-operating month or a 3-year rolling average basis and combusts more than 90% natural gas on a heat input basis on a 12-operating-month rolling average basis] | 50 kg CO2/GJ (120 lb CO2/MMBtu) of heat input. |
| Newly constructed and reconstructed stationary combustion turbine that combusts 90% or less natural gas on a heat input basis on a 12-operating-month rolling average basis | Between 50 to 69 kg CO2/GJ (120 to 160 lb CO2/MMBtu) of heat input as determined by the procedures in § 60.5525. |
[89 FR 40034, May 9, 2024]