[As stated in § 60.4210(g), manufacturers of fire pump engines may use the following test cycle for testing fire pump engines:]

Mode No.Engine speed 1Torque

(percent) 2
Weighting

factors
1Rated1000.30
2Rated750.50
3Rated500.20
1 Engine speed: ±2 percent of point.
2 Torque: NFPA certified nameplate HP for 100 percent point. All points should be ±2 percent of engine percent load value.