Table 6 to Subpart IIII of Part 60—Optional 3-Mode Test Cycle for Stationary Fire Pump Engines
[As stated in § 60.4210(g), manufacturers of fire pump engines may use the following test cycle for testing fire pump engines:]
| Mode No. | Engine speed 1 | Torque (percent) 2 | Weighting factors |
|---|
| 1 | Rated | 100 | 0.30 |
| 2 | Rated | 75 | 0.50 |
| 3 | Rated | 50 | 0.20
|
| 1 Engine speed: ±2 percent of point.
|
| 2 Torque: NFPA certified nameplate HP for 100 percent point. All points should be ±2 percent of engine percent load value. |