eCFR.io
Daily eCFR

Table 2 to Subpart C<span class="standard">b</span> of Part 60—Nitrogen Oxides Limits for Existing Designated Facilities Included in an Emissions Averaging Plan at a Municipal Waste Combustor Plant <sup>b</sup>

Table 2 to Subpart Cb of Part 60, Title 40

CitationTable 2 to Subpart Cb of Part 60, Title 40
CorpusDaily eCFR
Displayed edition2026-04-24
Last updated2026-04-24

Table 2 to Subpart Cb of Part 60—Nitrogen Oxides Limits for Existing Designated Facilities Included in an Emissions Averaging Plan at a Municipal Waste Combustor Plant b

Municipal waste combustor technologyBefore April 28, 2009,

nitrogen oxides emission limit

(parts per million by volume) b
On and after April 28, 2009,

nitrogen oxides emission limit

(parts per million by volume) a
Mass burn waterwall185185
Mass burn rotary waterwall220190
Refuse-derived fuel combustor230230
Fluidized bed combustor165165
a Mass burn refractory municipal waste combustors and other MWC technologies not listed above may not be included in an emissions averaging plan.
b Corrected to 7 percent oxygen, dry basis.

[71 FR 27334, May 10, 2006]

Authority42 U.S.C. 7401 et seq.
Source36 FR 24877, Dec. 23, 1971, unless otherwise noted.