Title 30
SECTION 77.901
77.901 Protection of low- and medium-voltage three-phase circuits.
§ 77.901 Protection of low- and medium-voltage three-phase circuits.(a) Low- and medium-voltage circuits supplying power to portable or mobile three-phase alternating equipment shall contain:
(1) Either a direct or derived neutral grounded through a suitable resistor at the power source;
(2) A grounding circuit originating at the grounded side of the grounding resistor which extends along with the power conductors and serves as a grounding conductor for the frames of all the electric equipment supplied power from the circuit.
(b) Grounding resistors, where required, shall be of an ohmic value which limits the ground fault current to no more than 25 amperes. Such grounding resistors shall be rated for maximum fault current continuously and provide insulation from ground for a voltage equal to the phase-to-phase voltage of the system.
(c) Low- and medium-voltage circuits supplying power to three-phase alternating current stationary electric equipment shall comply with the National Electric Code.