Appendix E to Subpart G of Part 431 - Uniform Test Method for the Measurement of Energy Efficiency of Commercial Heat Pump Water Heaters
10:3.0.1.4.19.7.64.6.55 : Appendix E
Appendix E to Subpart G of Part 431 - Uniform Test Method for the
Measurement of Energy Efficiency of Commercial Heat Pump Water
Heaters
Note: On and after November 6, 2017, manufacturers must
make any representations with respect to energy use or efficiency
of commercial heat pump water heaters in accordance with the
results of testing pursuant to this appendix.
1. General. Determine the COPh for commercial heat pump
water heaters (CHPWHs) using the test procedure set forth below.
Certain sections below reference ANSI/ASHRAE 118.1-2012
(incorporated by reference; see § 431.105). Where the instructions
contained below differ from those contained in ANSI/ASHRAE
118.1-2012, the sections in this appendix control.
2. Definitions and Symbols. The definitions and symbols
are as listed in section 3 of ANSI/ASHRAE 118.1-2012.
3. Instrumentation. The instruments required for the test
are as described in section 6 of ANSI/ASHRAE 118.1-2012 (except
sections 6.3, 6.4, and 6.6).
4. Test Set-Up. Follow the provisions described in this
section to install the CHPWH for testing. Use the test set-up and
installation instructions set forth for Type IV and Type V
equipment (as applicable), defined in sections 4.4 and 4.5 of
ANSI/ASHRAE 118.1-2012 and in accordance with the sections
below:
4.1. Test set-up and installation instructions.
4.1.1. For air-source CHPWHs, set up the unit for testing as per
section 7.1 and Figure 5a of ANSI/ASHRAE 118.1-2012 for CHPWHs
without an integral storage tank, and as per Figure 6 in section
7.7.1 of ANSI/ASHRAE 118.1-2012 for CHPWHs with an integral storage
tank.
4.1.2. For direct geo-exchange CHPWHs, set up the unit
for testing as per section 7.1 and Figure 5b of ASNI/ASHRAE
118.1-2012 for CHPWHs without an integral storage tank, and as per
Figure 7 in section 7.7.2 of ANSI/ASHRAE 118.1-2012 for CHPWHs with
an integral storage tank.
4.1.3. For indoor water-source, ground-source
closed-loop, and ground water-source CHPWHs, set up the unit for
testing as per section 7.1 and Figure 5c of ANSI/ASHRAE 118.1-2012
for CHPWHs without an integral storage tank, and as per Figure 8 in
section 7.7.3 of ANSI/ASHRAE 118.1-2012 for CHPWHs with an integral
storage tank.
4.2. Use the water piping instructions described in
section 7.2 of ANSI/ASHRAE 118.1-2012 and the special instructions
described in section 7.7.6 of ANSI/ASHRAE 118.1-2012. Insulate all
the pipes used for connections with material having a thermal
resistance of not less than 4 h· °F·ft 2/Btu for a total piping
length of not less than 4 feet from the water heater connection
ports.
4.3. Install the thermocouples, including the room
thermocouples, as per the instructions in sections 7.3.1, 7.3.2,
and 7.3.3 (as applicable) of ANSI/ASHRAE 118.1-2012.
4.4. Section 7.6 of ANSI/ASHRAE 118.1-2012 must be used if the
manufacturer neither submits nor specifies a water pump applicable
for the unit for laboratory testing.
4.5. Install the temperature sensors at the locations specified
in Figure 5a, 5b, 5c, 6, 7, or 8 of ANSI/ASHRAE 118.1-2012, as
applicable as per section 4.1 of this appendix. The sensor shall be
installed in such a manner that the sensing portion of the device
is positioned within the water flow and as close as possible to the
center line of the pipe. Follow the instructions provided in
sections 7.7.7.1 and 7.7.7.2 of ANSI/ASHRAE 118.1-2012 to install
the temperature and flow-sensing instruments.
4.6. Use the following evaporator side rating conditions as
applicable for each category of CHPWHs. These conditions are also
mentioned in Table 5.1 of this appendix:
4.6.1. For air-source CHPWHs, maintain the evaporator air
entering dry-bulb temperature at 80.6 °F ± 1 °F and wet-bulb
temperature at 71.2 °F ± 1 °F throughout the conduct of the
test.
4.6.2. For direct geo-exchange CHPWHs, maintain the evaporator
refrigerant temperature at 32 °F ± 1 °F.
4.6.3. For indoor water-source CHPWHs, maintain the evaporator
entering water temperature at 68 °F ± 1 °F.
4.6.4. For ground water-source CHPWHs, maintain the evaporator
entering water temperature at 50 °F ± 1 °F.
4.6.5. For ground-source closed-loop CHPWHs, maintain the
evaporator entering water temperature at 32 °F ± 1 °F.
4.6.5.1. For ground-source closed-loop CHPWHs, the evaporator
water must be mixed with 15-percent methanol by-weight to allow the
solution to achieve the rating conditions required in section
4.6.5.
4.7. The CHPWH being tested must be installed as per the
instructions specified in sections 4.1 to 4.6 (as applicable) of
this appendix. For all other installation requirements, use section
7.7.4 of ANSI/ASHRAE 118.1-2012 to resolve any issues related to
installation (other than what is specified in this test procedure)
of the equipment for testing. Do not make any alterations to the
equipment except as specified in this appendix for installation,
testing, and the attachment of required test apparatus and
instruments.
4.8. Use Table 3 of ANSI/ASHRAE 118.1-2012 for
measurement tolerances of various parameters.
4.9. If the CHPWH is equipped with a thermostat that is used to
control the throttling valve of the equipment, then use the
provisions in section 7.7.7.3 of ANSI/ASHRAE 118.1-2012 to set up
the thermostat.
4.10. For CHPWHs equipped with an integral storage tank,
supplemental heat inputs such as electric resistance elements must
be disabled as per section 7.7.8 of ANSI/ASHRAE 118.1-2012.
4.11. Install instruments to measure the electricity supply to
the equipment as specified in section 7.5 of ANSI/ASHRAE
118.1-2012.
5. Test Procedure
Test all CHPWHs that are not equipped with an integral storage
tank as per the provisions described in ANSI/ASHRAE 118.1-2012 for
“Type IV” equipment as defined in section 4.4 of ANSI/ASHRAE
118.1-2012. Test all CHPWHs that are equipped with an integral
storage tank as per the provisions described in ANSI/ASHRAE
118.1-2012 for “Type V” equipment as defined in section 4.5 of
ANSI/ASHRAE 118.1-2012. Tests for all CHPWHs must follow the steps
described below.
5.1. Supply the CHPWH unit with electricity at the voltage
specified by the manufacturer. Follow the provisions in section
8.2.1 of ANSI/ASHRAE 118.1-2012 to maintain the electricity supply
at the required level.
5.1.1. For models with multiple voltages specified by the
manufacturer, use the minimum voltage specified by the manufacturer
to conduct the test. Maintain the voltage as per the limits
specified in section 8.2.1 of ANSI/ASHRAE 118.1-2012. The test may
be repeated at other voltages at the manufacturer's discretion.
5.2. Set the condenser supply water temperature and outlet water
temperature per the following provisions and as set forth in Table
5.1 of this section:
Table 5.1 - Evaporator and Condenser Side
Rating Conditions
Category of CHPWH |
Evaporator side rating
conditions |
Condenser side rating
conditions |
Air-source
commercial heat pump water heater |
Evaporator entering air
conditions:
Dry bulb: 80.6 °F ± 1 °F
Wet bulb: 71.2 °F ± 1 °F |
Entering water temperature: 70
°F ± 1 °F. Vary water flow rate (if needed) to achieve the outlet
water temperature as specified in section 8.7.2 of ANSI/ASHRAE
118.1-2012. |
|
|
If the required outlet water
temperature as specified in section 8.7.2 of ANSI/ASHRAE 118.1-2012
is not met even after varying the flow rate, then change the
condenser entering water temperature to 110 °F ± 1 °F. Vary flow
rate to achieve the conditions in section 8.7.2 of ANSI/ASHRAE
118.1-2012. |
Direct
geo-exchange commercial heat pump water heater |
Evaporator refrigerant
temperature: 32 °F ± 1 °F |
Entering water temperature:
110 °F ± 1 °F. |
Indoor
water-source commercial heat pump water heater |
Evaporator entering water
temperature: 68 °F ± 1 °F |
Entering water temperature:
110 °F ± 1 °F. |
Ground
water-source commercial heat pump water heater |
Evaporator entering water
temperature: 50 °F ± 1 °F |
Entering water temperature:
110 °F ± 1 °F. |
Ground-source
closed-loop commercial heat pump water heater |
Evaporator entering water
temperature: 32 °F ± 1 °F |
Entering water temperature:
110 °F ± 1 °F. |
5.2.1. For air-source CHPWHs:
5.2.1.1. Set the supply water temperature to 70 °F ± 1 °F. The
water pressure must not exceed the maximum working pressure rating
for the equipment under test.
5.2.1.2. Use the provisions in section 8.7.1 of ANSI/ASHRAE
118.1-2012 to set the tank thermostat for CHPWHs equipped with an
integral storage tank.
5.2.1.3. Initiate operation at the rated pump flow rate and
measure the outlet water temperature. If the outlet water
temperature is maintained at 120 °F ± 5 °F with no variation in
excess of 2 °F over a three-minute period, as required by section
8.7.2 of ANSI/ASHRAE 118.1-2012, skip to section 5.3 of this
appendix.
5.2.1.4. If the outlet water temperature condition as specified
in section 8.7.2 of ANSI/ASHRAE 118.1-2012 is not achieved, adjust
the water flow rate over the range of the pump's capacity. If,
after varying the water flow rate, the outlet water temperature is
maintained at 120 °F ± 5 °F with no variation in excess of 2 °F
over a three-minute period, as required by section 8.7.2 of
ANSI/ASHRAE 118.1-2012, skip to section 5.3 of this appendix.
5.2.1.5. If, after adjusting the water flow rate within the
range that is achievable by the pump, the outlet water temperature
condition as specified in section 8.7.2 of ANSI/ASHRAE 118.1-2012
is still not achieved, then change the supply water temperature to
110 °F ± 1 °F and repeat the instructions from sections 5.2.1.2 and
5.2.1.4 of this appendix.
5.2.1. 6. If the outlet water temperature condition cannot be
met, then a test procedure waiver is necessary to specify an
alternative set of test conditions.
5.2.2. For direct geo-exchange, indoor water-source,
ground-source closed-loop, and ground water-source CHPWHs use the
following steps:
5.2.2.1. Set the condenser supply water temperature to 110 °F ±
1 °F. The water pressure must not exceed the maximum working
pressure rating for the equipment under test.
5.2.2.2. Use the provisions in section 8.7.1 of ANSI/ASHRAE
118.1-2012 to set the tank thermostat for CHPWHs equipped with an
integral storage tank.
5.2.2.3. Follow the steps specified in section 8.7.2 of
ANSI/ASHRAE 118.1-2012 to obtain an outlet water temperature of 120
°F ± 5 °F with no variation in excess of 2 °F over a three-minute
period.
5.3. Conduct the test as per section 9.1.1, “Full Input Rating,”
of ANSI/ASHRAE 118.1-2012. The flow rate, “FR,” referred to in
section 9.1.1 of ANSI/ASHRAE 118.1-2012 is the flow rate of water
through the CHPWH expressed in gallons per minute obtained after
following the steps in section 5.2 of this appendix. Use the
evaporator side rating conditions specified in section 4.6 of this
appendix to conduct the test as per section 9.1.1 of ANSI/ASHRAE
118.1-2012.
5.4. Calculate the COPh of the CHPWH according to section 10.3.1
of the ANSI/ASHRAE 118.1-2012 for the “Full Capacity Test Method.”
For all calculations, time differences must be expressed in
minutes.
[81 FR 79346, Nov. 10, 2016]