Appendix Z to Subpart B of Part 430 - Uniform Test Method for Measuring the Energy Consumption of External Power Supplies
10:3.0.1.4.18.3.13.6.38 : Appendix Z
Appendix Z to Subpart B of Part 430 - Uniform Test Method for
Measuring the Energy Consumption of External Power Supplies
Starting on February 21, 2016, any representations made with
respect to the energy use or efficiency of external power supplies
must be made in accordance with the results of testing pursuant to
this appendix. Prior to February 21, 2016, representations made
with respect to the energy use or efficiency of external power
supplies must be made in accordance with this appendix or Appendix
Z as it appeared at 10 CFR part 430, subpart B, Appendix Z as
contained in the 10 CFR parts 200 to 499 edition revised as of
January 1, 2015. Because representations must be made in accordance
with tests conducted pursuant to this appendix as of February 21,
2016, manufacturers may wish to begin using this test procedure as
soon as possible.
1. Scope.
This appendix covers the test requirements used to measure the
energy consumption of direct operation external power supplies and
indirect operation Class A external power supplies subject to the
energy conservation standards set forth at § 430.32(w)(1).
2. Definitions: The following definitions are for the
purposes of understanding terminology associated with the test
method for measuring external power supply energy consumption. For
clarity on any other terminology used in the test method, please
refer to IEC Standard 60050 or IEEE Standard 100. (Reference for
guidance only, see § 430.4.)
a. Active mode means the mode of operation when the
external power supply is connected to the main electricity supply
and the output is (or “all outputs are” for a multiple-voltage
external power supply) connected to a load (or “loads” for a
multiple-voltage external power supply).
b. Active mode efficiency is the ratio, expressed as a
percentage, of the total real output power produced by a power
supply to the real input power required to produce it. (Reference
for guidance only, see IEEE Standard 1515-2000, 4.3.1.1, §
430.4.)
c. Active power (P) (also real power) means the
average power consumed by a unit. For a two terminal device with
current and voltage waveforms i(t) and v(t) which are periodic with
period T, the real or active power P is:
d. Ambient temperature means the temperature of the
ambient air immediately surrounding the unit under test.
e. Apparent power (S) is the product of RMS voltage and
RMS current (VA).
f. Average Active-Mode Efficiency means the average of the
loading conditions (100 percent, 75 percent, 50 percent, and 25
percent of its nameplate output current) for which it can sustain
the output current.
g. IEC 62301 means the test standard published by the
International Electrotechnical Commission, titled “Household
electrical appliances - Measurement of standby power,” Publication
62301 (Edition 2.0 2011-01) (incorporated by reference; see §
430.3).
h. Instantaneous power means the product of the
instantaneous voltage and instantaneous current at a port (the
terminal pair of a load).
i. Manual on-off switch is a switch activated by the user
to control power reaching the device. This term does not apply to
any mechanical, optical, or electronic switches that automatically
disconnect mains power from the device when a load is disconnected
from the device, or that control power to the load itself.
j. Minimum output current means the minimum current that
must be drawn from an output bus for an external power supply to
operate within its specifications.
k. Multiple-voltage external power supply means an
external power supply that is designed to convert line voltage AC
input into more than one simultaneous lower-voltage output.
l. Nameplate input frequency means the AC input frequency
of the power supply as specified on the manufacturer's label on the
power supply housing.
m. Nameplate input voltage means the AC input voltage of
the power supply as specified on the manufacturer's label on the
power supply housing.
n. Nameplate output current means the current output of
the power supply as specified on the manufacturer's label on the
power supply housing (either DC or AC) or, if absent from the
housing, as provided by the manufacturer.
o. Nameplate output power means the power output of the
power supply as specified on the manufacturer's label on the power
supply housing or, if absent from the housing, as specified in
documentation provided by the manufacturer.
p. Nameplate output voltage means the voltage output of
the power supply as specified on the manufacturer's label on the
power supply housing (either DC or AC).
q. No-load mode means the mode of operation when an
external power supply is connected to the main electricity supply
and the output is (or “all outputs are” for a multiple-voltage
external power supply) not connected to a load (or “loads” for a
multiple-voltage external power supply).
r. Off mode is the condition, applicable only to units
with manual on-off switches, in which the external power supply is
(1) connected to the main electricity supply; (2) the output is not
connected to any load; and (3) all manual on-off switches are
turned off.
s. Output bus means any of the outputs of the power
supply to which loads can be connected and from which power can be
drawn, as opposed to signal connections used for communication.
t. Single-voltage external AC-AC power supply means an
external power supply that is designed to convert line voltage AC
input into lower voltage AC output and is able to convert to only
one AC output voltage at a time.
u. Single-voltage external AC-DC power supply means an
external power supply that is designed to convert line voltage AC
input into lower-voltage DC output and is able to convert to only
one DC output voltage at a time.
v. Standby mode means the condition in which the external
power supply is in no-load mode and, for external power supplies
with manual on-off switches, all such switches are turned on.
w. Switch-selectable single voltage external power supply
means a single-voltage AC-AC or AC-DC power supply that allows
users to choose from more than one output voltage.
x. Total harmonic distortion, expressed as a percentage,
is the RMS value of an AC signal after the fundamental component is
removed and interharmonic components are ignored, divided by the
RMS value of the fundamental component. THD of current is defined
as:
where
In is the RMS value of the
nth harmonic of the current signal.
y. True power factor (PF) is the ratio of the active
power (P) consumed in watts to the apparent power (S), drawn in
volt-amperes.
This definition of power factor includes the
effect of both distortion and displacement.
z. Unit under test is the external power supply being
tested.
3. Test Apparatus and General Instructions:
(a) Single-Voltage External Power Supply.
(i) Any power measurements recorded, as well as any power
measurement equipment utilized for testing, shall conform to the
uncertainty and resolution requirements outlined in Section 4,
“General conditions for measurements,” as well as Annexes B, “Notes
on the measurement of low power modes,” and D, “Determination of
uncertainty of measurement,” of IEC 62301 (incorporated by
reference; see § 430.3).
(ii) As is specified in IEC 62301 (incorporated by reference;
see § 430.3), the tests shall be carried out in a room that has an
air speed close to the unit under test (UUT) of ≤0.5 m/s. The
ambient temperature shall be maintained at 20 ± 5 °C throughout the
test. There shall be no intentional cooling of the UUT by use of
separately powered fans, air conditioners, or heat sinks. The UUT
shall be tested on a thermally non-conductive surface. Products
intended for outdoor use may be tested at additional temperatures,
provided those are in addition to the conditions specified above
and are noted in a separate section on the test report.
(iii) If the UUT is intended for operation on AC line-voltage
input in the United States, it shall be tested at 115 V at 60 Hz.
If the UUT is intended for operation on AC line-voltage input but
cannot be operated at 115 V at 60 Hz, it shall not be tested. The
input voltage shall be within ±1 percent of the above specified
voltage.
(iv) The input voltage source must be capable of delivering at
least 10 times the nameplate input power of the UUT as is specified
in IEEE 1515-2000 (Referenced for guidance only, see § 430.4).
Regardless of the AC source type, the THD of the supply voltage
when supplying the UUT in the specified mode must not exceed 2%, up
to and including the 13th harmonic (as specified in IEC 62301). The
peak value of the test voltage must be within 1.34 and 1.49 times
its RMS value (as specified in IEC 62301 (incorporated by
reference; see § 430.3)).
(v) Select all leads used in the test set-up as specified in
Table B.2 - “Commonly used values for wire gages and related
voltage drops” in IEEE 15152000.
(b) Multiple-Voltage External Power Supply. Unless otherwise
specified, measurements shall be made under test conditions and
with equipment specified below.
(i) Verifying Accuracy and Precision of Measuring Equipment
(A) Any power measurements recorded, as well as any power
measurement equipment utilized for testing, must conform to the
uncertainty and resolution requirements outlined in Section 4,
“General conditions for measurements”, as well as Annexes B, “Notes
on the measurement of low power modes”, and D, “Determination of
uncertainty of measurement”, of IEC 62301 (incorporated by
reference; see § 430.3).
(B) [Reserved]
(ii) Setting Up the Test Room
All tests shall be carried out in a room with an air speed
immediately surrounding the UUT of ≤0.5 m/s. The ambient
temperature shall be maintained at 20 °C ±5 °C throughout the test.
There shall be no intentional cooling of the UUT such as by use of
separately powered fans, air conditioners, or heat sinks. The UUT
shall be conditioned, rested, and tested on a thermally
non-conductive surface. A readily available material such as
Styrofoam will be sufficient.
(iii) Verifying the UUT's Input Voltage and Input Frequency
(A) If the UUT is intended for operation on AC line-voltage
input in the United States, it shall be tested at 115 V at 60 Hz.
If the UUT is intended for operation on AC line-voltage input but
cannot be operated at 115 V at 60 Hz, it shall not be tested. The
input voltage shall be within ±1 percent of the above specified
voltage.
(B) If the input voltage is AC, the input frequency shall be
within ±1 percent of the specified frequency. The THD of the input
voltage shall be ≤2 percent, up to and including the 13th harmonic.
The crest factor of the input voltage shall be between 1.34 and
1.49.
4. Test Measurement:
(a) Single-Voltage External Power Supply
(i) Standby Mode and Active-Mode Measurement.
(A) Any built-in switch in the UUT controlling power flow to the
AC input must be in the “on” position for this measurement, and
note the existence of such a switch in the final test report. Test
power supplies packaged for consumer use to power a product with
the DC output cord supplied by the manufacturer. There are two
options for connecting metering equipment to the output of this
type of power supply: Cut the cord immediately adjacent to the DC
output connector, or attach leads and measure the efficiency from
the output connector itself. If the power supply is attached
directly to the product that it is powering, cut the cord
immediately adjacent to the powered product and connect DC
measurement probes at that point. Any additional metering equipment
such as voltmeters and/or ammeters used in conjunction with
resistive or electronic loads must be connected directly to the end
of the output cable of the UUT. If the product has more than two
output wires, including those that are necessary for controlling
the product, the manufacturer must supply a connection diagram or
test fixture that will allow the testing laboratory to put the unit
under test into active-mode. Figure 1 provides one illustration of
how to set up an EPS for test; however, the actual test setup may
vary pursuant to the requirements of this paragraph.
(B) External power supplies must be tested in their final,
completed configuration in order to represent their measured
efficiency on product labels or specification sheets. Although the
same procedure may be used to test the efficiency of a bare circuit
board power supply prior to its incorporation into a finished
housing and the attachment of its DC output cord, the efficiency of
the bare circuit board power supply may not be used to characterize
the efficiency of the final product (once enclosed in a case and
fitted with a DC output cord). For example, a power supply
manufacturer or component manufacturer may wish to assess the
efficiency of a design that it intends to provide to an OEM for
incorporation into a finished external power supply, but these
results may not be used to represent the efficiency of the finished
external power supply.
(C) All single voltage external AC-DC power supplies have a
nameplate output current. This is the value used to determine the
four active-mode load conditions and the no load condition required
by this test procedure. The UUT shall be tested at the following
load conditions:
Table 1 - Loading Conditions for a
Single-Voltage Unit Under Test
Percentage of Nameplate Output Current |
Load Condition
1 |
100% of Nameplate Output
Current ±2%. |
Load Condition
2 |
75% of Nameplate Output
Current ±2%. |
Load Condition
3 |
50% of Nameplate Output
Current ±2%. |
Load Condition
4 |
25% of Nameplate Output
Current ±2%. |
Load Condition
5 |
0%. |
The 2% allowance is of nameplate output current, not of the
calculated current value. For example, a UUT at Load Condition 3
may be tested in a range from 48% to 52% of rated output current.
Additional load conditions may be selected at the technician's
discretion, as described in IEEE 1515-2000 (Referenced for guidance
only, see § 430.4), but are not required by this test procedure.
For Loading Condition 5, place the UUT in no-load mode, disconnect
any additional signal connections to the UUT, and measure input
power.
1. Where the external power supply lists both an instantaneous
and continuous output current, test the external power supply at
the continuous condition only.
2. If an external power supply cannot sustain output at one or
more of loading conditions 1-4 as specified in Table 1, test the
external power supply only at the loading conditions for which it
can sustain output. In these cases, the average active mode
efficiency is the average of the loading conditions for which it
can sustain the output.
(D) Test switch-selectable single-voltage external power
supplies twice - once at the highest nameplate output voltage and
once at the lowest.
(E) Test adaptive external power supplies twice - once at the
highest achievable output voltage and once at the lowest.
(F) In order to load the power supply to produce all four
active-mode load conditions, use a set of variable resistive or
electronic loads. Although these loads may have different
characteristics than the electronic loads power supplies are
intended to power, they provide standardized and readily repeatable
references for testing and product comparison. Note that resistive
loads need not be measured precisely with an ohmmeter; simply
adjust a variable resistor to the point where the ammeter confirms
that the desired percentage of nameplate output current is flowing.
For electronic loads, adjust the desired output current in constant
current (CC) mode rather than adjusting the required output power
in constant power (CP) mode.
(G) As noted in IEC 62301 (incorporated by reference; see §
430.3), instantaneous measurements are appropriate when power
readings are stable in a particular load condition. Operate the UUT
at 100% of nameplate current output for at least 30 minutes
immediately prior to conducting efficiency measurements. After this
warm-up period, monitor AC input power for a period of 5 minutes to
assess the stability of the UUT. If the power level does not drift
by more than 5% from the maximum value observed, the UUT is
considered stable and the measurements should be recorded at the
end of the 5-minute period. Measure subsequent load conditions
under the same 5-minute stability parameters. Note that only one
warm-up period of 30 minutes is required for each UUT at the
beginning of the test procedure. If the AC input power is not
stable over a 5-minute period, follow the guidelines established by
IEC 62301 for measuring average power or accumulated energy over
time for both AC input and DC output. Conduct efficiency
measurements in sequence from Load Condition 1 to Load Condition 5
as indicated in Table 1. If testing of additional, optional load
conditions is desired, that testing should be conducted in
accordance with this test procedure and subsequent to completing
the sequence described above.
(H) Calculate efficiency by dividing the UUT's measured DC
output power at a given load condition by the true AC input power
measured at that load condition. Calculate average efficiency as
the arithmetic mean of the efficiency values calculated at Test
Conditions 1, 2, 3, and 4 in Table 1, and record this value.
Average efficiency for the UUT is a simple arithmetic average of
active-mode efficiency values, and is not intended to represent
weighted average efficiency, which would vary according to the duty
cycle of the product powered by the UUT.
(I) Power consumption of the UUT at each Load Condition 1-4 is
the difference between the DC output power (W) at that Load
Condition and the AC input power (W) at that Load Condition. The
power consumption of Load Condition 5 (no load) is equal to the AC
input power (W) at that Load Condition.
(ii) Off-Mode Measurement - If the external power supply UUT
incorporates manual on-off switches, place the UUT in off-mode, and
measure and record its power consumption at “Load Condition 5” in
Table 1. The measurement of the off-mode energy consumption must
conform to the requirements specified in paragraph 4(a)(i) of this
appendix, except that all manual on-off switches must be placed in
the “off” position for the off-mode measurement. The UUT is
considered stable if, over 5 minutes with samples taken at least
once every second, the AC input power does not drift from the
maximum value observed by more than 1 percent or 50 milliwatts,
whichever is greater. Measure the off-mode power consumption of a
switch-selectable single-voltage external power supply twice - once
at the highest nameplate output voltage and once at the lowest.
(b) Multiple-Voltage External Power Supply - Power supplies must
be tested with the output cord packaged with the unit for sale to
the consumer, as it is considered part of the unit under test.
There are two options for connecting metering equipment to the
output of this type of power supply: cut the cord immediately
adjacent to the output connector or attach leads and measure the
efficiency from the output connector itself. If the power supply is
attached directly to the product that it is powering, cut the cord
immediately adjacent to the powered product and connect output
measurement probes at that point. The tests should be conducted on
the sets of output wires that constitute the output busses. If the
product has additional wires, these should be left electrically
disconnected unless they are necessary for controlling the product.
In this case, the manufacturer shall supply a connection diagram or
test fixture that will allow the testing laboratory to put the unit
under test into active mode.
(i) Standby-Mode and Active-Mode Measurement - The measurement
of the multiple-voltage external power supply standby mode (also
no-load-mode) energy consumption and active-mode efficiency shall
be as follows:
(A) Loading conditions and testing sequence. (1) If the unit
under test has on-off switches, all switches shall be placed in the
“on” position. Loading criteria for multiple-voltage external power
supplies shall be based on nameplate output current and not on
nameplate output power because output voltage might not remain
constant.
(2) The unit under test shall operate at 100 percent of
nameplate current output for at least 30 minutes immediately before
conducting efficiency measurements.
(3) After this warm-up period, the technician shall monitor AC
input power for a period of 5 minutes to assess the stability of
the unit under test. If the power level does not drift by more than
1 percent from the maximum value observed, the unit under test can
be considered stable and measurements can be recorded at the end of
the 5-minute period. Measurements at subsequent loading conditions,
listed in Table 1, can then be conducted under the same 5-minute
stability guidelines. Only one warm-up period of 30 minutes is
required for each unit under test at the beginning of the test
procedure.
(4) If AC input power is not stable over a 5-minute period, the
technician shall follow the guidelines established by IEC Standard
62301 for measuring average power or accumulated energy over time
for both input and output. (Reference for guidance only, see §
430.4).
(5) The unit under test shall be tested at the loading
conditions listed in Table 1, derated per the proportional
allocation method presented in the following section.
Table 1 - Loading Conditions for Unit Under
Test
Loading Condition
1 |
100% of Derated Nameplate
Output Current ±2%. |
Loading Condition
2 |
75% of Derated Nameplate
Output Current ±2%. |
Loading Condition
3 |
50% of Derated Nameplate
Output Current ±2%. |
Loading Condition
4 |
25% of Derated Nameplate
Output Current ±2%. |
Loading Condition
5 |
0%. |
(6) Input and output power measurements shall be conducted in
sequence from Loading Condition 1 to Loading Condition 4, as
indicated in Table 1. For Loading Condition 5, the unit under test
shall be placed in no-load mode, any additional signal connections
to the unit under test shall be disconnected, and input power shall
be measured.
(B) Proportional allocation method for loading multiple-voltage
external power supplies. For power supplies with multiple voltage
busses, defining consistent loading criteria is difficult because
each bus has its own nameplate output current. The sum of the power
dissipated by each bus loaded to its nameplate output current may
exceed the overall nameplate output power of the power supply. The
following proportional allocation method must be used to provide
consistent loading conditions for multiple-voltage external power
supplies. For additional explanation, please refer to section 6.1.1
of the California Energy Commission's “Proposed Test Protocol for
Calculating the Energy Efficiency of Internal Ac-Dc Power Supplies
Revision 6.2,” November 2007.
(1) Consider a multiple-voltage power supply with N
output busses, and nameplate output voltages V1, * * *,
VN, corresponding output current ratings I1, * * *,
IN, and a nameplate output power P. Calculate the
derating factor D by dividing the power supply nameplate
output power P by the sum of the nameplate output powers of
the individual output busses, equal to the product of bus nameplate
output voltage and current IiVi, as follows:
(2) If D ≥1, then loading every bus to its nameplate
output current does not exceed the overall nameplate output power
for the power supply. In this case, each output bus will simply be
loaded to the percentages of its nameplate output current listed in
Table 1. However, if D <1, it is an indication that
loading each bus to its nameplate output current will exceed the
overall nameplate output power for the power supply. In this case,
and at each loading condition, each output bus will be loaded to
the appropriate percentage of its nameplate output current listed
in Table 1, multiplied by the derating factor D.
(C) Minimum output current requirements. Depending on their
application, some multiple-voltage power supplies may require a
minimum output current for each output bus of the power supply for
correct operation. In these cases, ensure that the load current for
each output at Loading Condition 4 in Table 1 is greater than the
minimum output current requirement. Thus, if the test method's
calculated load current for a given voltage bus is smaller than the
minimum output current requirement, the minimum output current must
be used to load the bus. This load current shall be properly
recorded in any test report.
(D) Test loads. Active loads such as electronic loads or passive
loads such as rheostats used for efficiency testing of the unit
under test shall be able to maintain the required current loading
set point for each output voltage within an accuracy of ±0.5
percent. If electronic load banks are used, their settings should
be adjusted such that they provide a constant current load to the
unit under test.
(E) Efficiency calculation. Efficiency shall be calculated by
dividing the measured active output power of the unit under test at
a given loading condition by the active AC input power measured at
that loading condition. Efficiency shall be calculated at each
Loading Condition (1, 2, 3, and 4, in Table 1) and be recorded
separately.
(F) Power consumption calculation. Power consumption of the unit
under test at Loading Conditions 1, 2, 3, and 4 is the difference
between the active output power at that Loading Condition and the
active AC input power at that Loading Condition. The power
consumption of Loading Condition 5 (no-load) is equal to the AC
active input power at that Loading Condition.
(ii) Off Mode Measurement - If the multiple-voltage external
power supply unit under test incorporates any on-off switches, the
unit under test shall be placed in off mode and its power
consumption in off mode measured and recorded. The measurement of
the off mode energy consumption shall conform to the requirements
specified in paragraph (4)(b)(i) of this appendix. Note that the
only loading condition that will be measured for off mode is
“Loading Condition 5” in paragraph (A), “Loading conditions and
testing sequence”, except that all manual on-off switches shall be
placed in the off position for the measurement.
[71 FR 71366, Dec. 8, 2006, as amended at 74 FR 12066, Mar. 23,
2009; 74 FR 13334, Mar. 27, 2009; 76 FR 31782, June 1, 2011; 80 FR
51441, Aug. 25, 2015]