Appendix B to Subpart B of Part 430 - Uniform Test Method for Measuring the Energy Consumption of Freezers
10:3.0.1.4.18.2.13.6.8 : Appendix B
Appendix B to Subpart B of Part 430 - Uniform Test Method for
Measuring the Energy Consumption of Freezers Note:
For freezers, the rounding requirements specified in sections
5.3.e and 6.1 of this appendix are not required for use until the
compliance date of any amended energy conservation standards for
these products.
1. Definitions
Section 3, Definitions, of HRF-1-2008 (incorporated by
reference; see § 430.3) applies to this test procedure.
Adjusted total volume means the product of the freezer
volume as defined in HRF-1-2008 (incorporated by reference; see §
430.3) in cubic feet multiplied by an adjustment factor.
Anti-sweat heater means a device incorporated into the
design of a freezer to prevent the accumulation of moisture on
exterior or interior surfaces of the cabinet.
Anti-sweat heater switch means a user-controllable switch
or user interface which modifies the activation or control of
anti-sweat heaters.
Automatic defrost means a system in which the defrost
cycle is automatically initiated and terminated, with resumption of
normal refrigeration at the conclusion of defrost operation. The
system automatically prevents the permanent formation of frost on
all refrigerated surfaces. Nominal refrigerated food temperatures
are maintained during the operation of the automatic defrost
system.
Automatic icemaker means a device that can be supplied
with water without user intervention, either from a pressurized
water supply system or by transfer from a water reservoir that
automatically produces, harvests, and stores ice in a storage bin,
with means to automatically interrupt the harvesting operation when
the ice storage bin is filled to a pre-determined level.
Complete temperature cycle means a time period defined
based upon the cycling of compartment temperature that starts when
the compartment temperature is at a maximum and ends when the
compartment temperature returns to an equivalent maximum (within
0.5 °F of the starting temperature), having in the interim fallen
to a minimum and subsequently risen again to reach the second
maximum. Alternatively, a complete temperature cycle can be defined
to start when the compartment temperature is at a minimum and end
when the compartment temperature returns to an equivalent minimum
(within 0.5 °F of the starting temperature), having in the interim
risen to a maximum and subsequently fallen again to reach the
second minimum.
Cycle means the period of 24 hours for which the energy
use of a freezer is calculated as though the consumer-activated
compartment temperature controls were set to maintain the
standardized temperature (see section 3.2 of this appendix).
Cycle type means the set of test conditions having the
calculated effect of operating a freezer for a period of 24 hours
with the consumer-activated controls other than the compartment
temperature control set to establish various operating
characteristics.
HRF-1-2008 means AHAM Standard HRF-1-2008, Association of
Home Appliance Manufacturers, Energy and Internal Volume of
Refrigerating Appliances (2008), including Errata to Energy and
Internal Volume of Refrigerating Appliances, Correction Sheet
issued November 17, 2009. Only sections of HRF-1-2008 (incorporated
by reference; see § 430.3) specifically referenced in this test
procedure are part of this test procedure. In cases where there is
a conflict, the language of the test procedure in this appendix
takes precedence over HRF-1-2008.
Ice storage bin means a container in which ice can be
stored.
Long-time automatic defrost means an automatic defrost
system where successive defrost cycles are separated by 14 hours or
more of compressor operating time.
Precooling means operating a refrigeration system before
initiation of a defrost cycle to reduce one or more compartment
temperatures significantly (more than 0.5 °F) below its minimum
during stable operation between defrosts.
Quick freeze means an optional feature on freezers that
is initiated manually. It bypasses the thermostat control and
operates continually until the feature is terminated either
manually or automatically.
Recovery means operating a refrigeration system after the
conclusion of a defrost cycle to reduce the temperature of one or
more compartments to the temperature range that the compartment(s)
exhibited during stable operation between defrosts.
Separate auxiliary compartment means a freezer
compartment other than the primary freezer compartment of a freezer
having more than one compartment. Access to a separate auxiliary
compartment is through a separate exterior door or doors rather
than through the door or doors of another compartment. Separate
auxiliary freezer compartments may not be larger than the primary
freezer compartment.
Special compartment means any compartment without doors
directly accessible from the exterior, and with separate
temperature control that is not convertible from fresh food
temperature range to freezer temperature range.
Stabilization period means the total period of time
during which steady-state conditions are being attained or
evaluated.
Stable operation means operation after steady-state
conditions have been achieved but excluding any events associated
with defrost cycles. During stable operation the average rate of
change of compartment temperature must not exceed 0.042 °F (0.023
°C) per hour. Such a calculation performed for compartment
temperatures at any two times, or for any two periods of time
comprising complete cycles, during stable operation must meet this
requirement.
(a) If compartment temperatures do not cycle, the relevant
calculation shall be the difference between the temperatures at two
points in time divided by the difference, in hours, between those
points in time.
(b) If compartment temperatures cycle as a result of compressor
cycling or other cycling operation of any system component
(e.g., a damper, fan, or heater), the relevant calculation
shall be the difference between compartment temperature averages
evaluated for whole compressor cycles or complete temperature
cycles divided by the difference, in hours, between either the
starts, ends, or mid-times of the two cycles.
Standard cycle means the cycle type in which the
anti-sweat heater switch, when provided, is set in the highest
energy-consuming position.
Through-the-door ice/water dispenser means a device
incorporated within the cabinet, but outside the boundary of the
refrigerated space, that delivers to the user on demand ice and may
also deliver water from within the refrigerated space without
opening an exterior door. This definition includes dispensers that
are capable of dispensing ice and water or ice only.
Variable defrost control means an automatic defrost
system in which successive defrost cycles are determined by an
operating condition variable (or variables) other than solely
compressor operating time. This includes any electrical or
mechanical device performing this function. A control scheme that
changes the defrost interval from a fixed length to an extended
length (without any intermediate steps) is not considered a
variable defrost control. A variable defrost control feature should
predict the accumulation of frost on the evaporator and react
accordingly. Therefore, the times between defrost must vary with
different usage patterns and include a continuum of lengths of time
between defrosts as inputs vary.
2. Test Conditions
2.1 Ambient Temperature Measurement. Temperature measuring
devices shall be shielded so that indicated temperatures are not
affected by the operation of the condensing unit or adjacent
units.
2.1.1 Ambient Temperature. The ambient temperature shall be
recorded at points located 3 feet (91.5 cm) above the floor and 10
inches (25.4 cm) from the center of the two sides of the unit under
test. The ambient temperature shall be 90.0 ±1.0 °F (32.2 ±0.6 °C)
during the stabilization period and the test period.
2.1.2 Ambient Temperature Gradient. The test room vertical
ambient temperature gradient in any foot of vertical distance from
2 inches (5.1 cm) above the floor or supporting platform to a
height of 1 foot (30.5 cm) above the top of the unit under test is
not to exceed 0.5 °F per foot (0.9 °C per meter). The vertical
ambient temperature gradient at locations 10 inches (25.4 cm) out
from the centers of the two sides of the unit being tested is to be
maintained during the test. To demonstrate that this requirement
has been met, test data must include measurements taken using
temperature sensors at locations 10 inches (25.4 cm) from the
center of the two sides of the unit under test at heights of 2
inches (5.1 cm) and 36 inches (91.4 cm) above the floor or
supporting platform and at a height of 1 foot (30.5 cm) above the
unit under test.
2.1.3 Platform. A platform must be used if the floor temperature
is not within 3 °F (1.7 °C) of the measured ambient temperature. If
a platform is used, it is to have a solid top with all sides open
for air circulation underneath, and its top shall extend at least 1
foot (30.5 cm) beyond each side and front of the unit under test
and extend to the wall in the rear.
2.2 Operational Conditions. The freezer shall be installed and
its operating conditions maintained in accordance with HRF-1-2008
(incorporated by reference; see § 430.3), sections 5.3.2 through
section 5.5.5.5 (but excluding sections 5.5.5.2 and 5.5.5.4). The
quick freeze option shall be switched off except as specified in
section 3.1 of this appendix. Additional clarifications are noted
in sections 2.3 through 2.9 of this appendix.
2.3 Anti-Sweat Heaters. The anti-sweat heater switch is to be on
during one test and off during a second test. In the case of a
freezer with variable anti-sweat heater control, the standard cycle
energy use shall be the result of the calculation described in
6.2.3.
2.4 The cabinet and its refrigerating mechanism shall be
assembled and set up in accordance with the printed consumer
instructions supplied with the cabinet. Set-up of the freezer shall
not deviate from these instructions, unless explicitly required or
allowed by this test procedure. Specific required or allowed
deviations from such set-up include the following:
(a) Connection of water lines and installation of water filters
are not required;
(b) Clearance requirements from surfaces of the product shall be
as described in section 2.6 below;
(c) The electric power supply shall be as described in
HRF-1-2008 (incorporated by reference; see § 430.3) section
5.5.1;
(d) Temperature control settings for testing shall be as
described in section 3 of this appendix. Settings for special
compartments shall be as described in section 2.5 of this
appendix;
(e) The product does not need to be anchored or otherwise
secured to prevent tipping during energy testing;
(f) All the product's chutes and throats required for the
delivery of ice shall be free of packing, covers, or other
blockages that may be fitted for shipping or when the icemaker is
not in use; and
(g) Ice storage bins shall be emptied of ice.
For cases in which set-up is not clearly defined by this test
procedure, manufacturers must submit a petition for a waiver (see
section 7).
2.5 Special compartments shall be tested with controls set to
provide the coldest temperature. However, for special compartments
in which temperature control is achieved using the addition of heat
(including resistive electric heating, refrigeration system waste
heat, or heat from any other source, but excluding the transfer of
air from another part of the interior of the product) for any part
of the controllable temperature range of that compartment, the
product energy use shall be determined by averaging two sets of
tests. The first set of tests shall be conducted with such special
compartments at their coldest settings, and the second set of tests
shall be conducted with such special compartments at their warmest
settings. The requirements for the warmest or coldest temperature
settings of this section do not apply to features or functions
associated with temperature control (such as quick freeze) that are
initiated manually and terminated automatically within 168
hours.
Movable subdividing barriers that separate compartments of
different types (e.g., fresh food on one side and cooler on
the other side) shall be placed in the median position. If such a
subdividing barrier has an even number of positions, the
near-median position representing the smallest volume of the warmer
compartment(s) shall be used.
2.6 Rear Clearance.
(a) General. The space between the lowest edge of the rear plane
of the cabinet and a vertical surface (the test room wall or
simulated wall) shall be the minimum distance in accordance with
the manufacturer's instructions, unless other provisions of this
section apply. The rear plane shall be considered to be the largest
flat surface at the rear of the cabinet, excluding features that
protrude beyond this surface, such as brackets or compressors.
(b) Maximum clearance. The clearance shall not be greater than 2
inches (51 mm) from the lowest edge of the rear plane to the
vertical surface, unless the provisions of subsection (c) of this
section apply.
(c) If permanent rear spacers or other components that protrude
beyond the rear plane extend further than the 2 inch (51 mm)
distance, or if the highest edge of the rear plane is in contact
with the vertical surface when the unit is positioned with the
lowest edge of the rear plane at or further than the 2 inch (51 mm)
distance from the vertical surface, the appliance shall be located
with the spacers or other components protruding beyond the rear
plane, or the highest edge of the rear plane, in contact with the
vertical surface.
(d) Rear-mounted condensers. If the product has a flat
rear-wall-mounted condenser (i.e., a rear-wall-mounted
condenser with all refrigerant tube centerlines within 0.25 inches
(6.4 mm) of the condenser plane), and the area of the condenser
plane represents at least 25% of the total area of the rear wall of
the cabinet, then the spacing to the vertical surface may be
measured from the lowest edge of the condenser plane.
2.7 Steady State Condition. Steady-state conditions exist if the
temperature measurements taken at 4-minute intervals or less during
a stabilization period are not changing at a rate greater than
0.042 °F (0.023 °C) per hour as determined by the applicable
condition of A or B described below.
A - The average of the measurements during a 2-hour period if no
cycling occurs or during a number of complete repetitive compressor
cycles occurring through a period of no less than 2 hours is
compared to the average over an equivalent time period with 3 hours
elapsing between the two measurement periods.
B - If A above cannot be used, the average of the measurements
during a number of complete repetitive compressor cycles occurring
through a period of no less than 2 hours and including the last
complete cycle before a defrost period (or if no cycling occurs,
the average of the measurements during the last 2 hours before a
defrost period) are compared to the same averaging period before
the following defrost period.
2.8 Freezers with Demand-Response Capability. Freezers that have
a communication module for demand-response functions that is
located within the cabinet shall be tested with the communication
module in the configuration set at the factory just before
shipping.
2.9 For products that require the freezer compartment to be
loaded with packages in accordance with section 5.5.5.3 of
HRF-1-2008, the number of packages comprising the 75% load shall be
determined by filling the compartment completely with the packages
that are to be used for the test, such that the packages fill as
much of the usable refrigerated space within the compartment as is
physically possible, and then removing from the compartment a
number of packages so that the compartment contains 75% of the
packages that were placed in the compartment to completely fill it.
If multiplying the total number of packages by 0.75 results in a
fraction, the number of packages used shall be rounded to the
nearest whole number, rounding up if the result ends in 0.5. For
multi-shelf units, this method shall be applied to each shelf. For
both single- and multi-shelf units, the remaining packages shall be
arranged as necessary to provide the required air gap and
thermocouple placement. The number of packages comprising the 100%
and 75% loading conditions shall be recorded in the test data
maintained in accordance with 10 CFR 429.71.
3. Test Control Settings
3.1 Model with No User Operable Temperature Control. A test
shall be performed during which the compartment temperature and
energy use shall be measured. A second test shall be performed with
the temperature control electrically short circuited to cause the
compressor to run continuously. If the model has the quick freeze
option, this option must be used to bypass the temperature
control.
3.2 Model with User Operable Temperature Control. Testing shall
be performed in accordance with one of the following sections using
the standardized temperature of 0.0 °F (−17.8 °C).
For the purposes of comparing compartment temperatures with
standardized temperatures, as described in sections 3.2.1 and
3.2.2, the freezer compartment temperature shall be as specified in
section 5.1.3.
3.2.1 A first test shall be performed with all temperature
controls set at their median position midway between their warmest
and coldest settings. For mechanical control systems, (a) knob
detents shall be mechanically defeated if necessary to attain a
median setting, and (b) the warmest and coldest settings shall
correspond to the positions in which the indicator is aligned with
control symbols indicating the warmest and coldest settings. For
electronic control systems, the test shall be performed with all
compartment temperature controls set at the average of the coldest
and warmest settings; if there is no setting equal to this average,
the setting closest to the average shall be used. If there are two
such settings equally close to the average, the higher of these
temperature control settings shall be used. A second test shall be
performed with all controls set at either their warmest or their
coldest setting (not electrically or mechanically bypassed),
whichever is appropriate, to attempt to achieve compartment
temperatures measured during the two tests that bound (i.e.,
one is above and one is below) the standardized temperature. If the
compartment temperatures measured during these two tests bound the
standardized temperature, then these test results shall be used to
determine energy consumption. If the compartment temperature
measured with all controls set at their coldest setting is above
the standardized temperature, the tested unit fails the test and
cannot be rated. If the compartment temperature measured with all
controls set at their warmest setting is below the standardized
temperature, then the result of this test alone will be used to
determine energy consumption. Also see Table 1 of this appendix,
which summarizes these requirements.
Table 1 - Temperature Settings for
Freezers
First test |
Second test |
Energy
calculation based on: |
Settings |
Results |
Settings |
Results |
Mid |
Low |
Warm |
Low |
Second Test Only. |
|
|
|
High |
First and Second Tests. |
|
High |
Cold |
Low |
First and Second Tests. |
|
|
|
High |
No Energy Use Rating. |
3.2.2 Alternatively, a first test may be performed with all
temperature controls set at their warmest setting. If the
compartment temperature is below the standardized temperature, then
the result of this test alone will be used to determine energy
consumption. If this condition is not met, then the unit shall be
tested in accordance with section 3.2.1.
4. Test Period
Tests shall be performed by establishing the conditions set
forth in section 2 and using the control settings as set forth in
section 3 above.
4.1 Non-automatic Defrost. If the model being tested has no
automatic defrost system, the test period shall start after
steady-state conditions (see section 2.7 of this appendix) have
been achieved and be no less than three hours in duration. During
the test period, the compressor motor shall complete two or more
whole compressor cycles. (A whole compressor cycle is a complete
“on” and a complete “off” period of the motor.) If no “off” cycling
occurs, the test period shall be three hours. If less than two
compressor cycles occur during a 24-hour period, then a single
complete compressor cycle may be used.
4.2 Automatic Defrost. If the model being tested has an
automatic defrost system, the test time period shall start after
steady-state conditions have been achieved and be from one point
during a defrost period to the same point during the next defrost
period. If the model being tested has a long-time automatic defrost
system, the alternate provisions of 4.2.1 may be used. If the model
being tested has a variable defrost control, the provisions of
4.2.2 shall apply.
4.2.1 Long-time Automatic Defrost. If the model being tested has
a long-time automatic defrost system, the two-part test described
in this section may be used. The first part is a stable period of
compressor operation that includes no portions of the defrost
cycle, such as precooling or recovery, that is otherwise the same
as the test for a unit having no defrost provisions (section 4.1).
The second part is designed to capture the energy consumed during
all of the events occurring with the defrost control sequence that
are outside of stable operation.
4.2.1.1 Cycling Compressor System. For a system with a cycling
compressor, the second part of the test starts at the termination
of the last regular compressor “on” cycle. The average temperature
of the compartment measured from the termination of the previous
compressor “on” cycle to the termination of the last regular
compressor “on” cycle must be within 0.5 °F (0.3 °C) of the average
temperature of the compartment measured for the first part of the
test. If any compressor cycles occur prior to the defrost heater
being energized that cause the average temperature in the
compartment to deviate from the average temperature for the first
part of the test by more than 0.5 °F (0.3 °C), these compressor
cycles are not considered regular compressor cycles and must be
included in the second part of the test. As an example, a
“precooling” cycle, which is an extended compressor cycle that
lowers the compartment temperature prior to energizing the defrost
heater, must be included in the second part of the test. The test
period for the second part of the test ends at the termination of
the first regular compressor “on” cycle after the compartment
temperatures have fully recovered to their stable conditions. The
average temperature of the compartment measured from this
termination of the first regular compressor “on” cycle until the
termination of the next regular compressor “on” cycle must be
within 0.5 °F (0.3 °C) of the average temperature of the
compartment measured for the first part of the test. See Figure 1.
Note that Figure 1 illustrates the concepts of precooling and
recovery but does not represent all possible defrost cycles.
4.2.1.2 Non-cycling Compressor System. For a system with a
non-cycling compressor, the second part of the test starts at a
time before defrost during stable operation when the compartment
temperature is within 0.5 °F (0.3 °C) of the average temperature of
the compartment measured for the first part of the test. The second
part stops at a time after defrost during stable operation when the
compartment temperature is within 0.5 °F (0.3 °C) of the average
temperature of the compartment measured for the first part of the
test. See Figure 2.
4.2.2 Variable Defrost Control. If the model being tested has a
variable defrost control system, the test shall consist of the same
two parts as the test for long-time automatic defrost (section
4.2.1).
5. Test Measurements
5.1 Temperature Measurements. (a) Temperature measurements shall
be made at the locations prescribed in Figure 5.2 of HRF-1-2008
(incorporated by reference; see § 430.3) and shall be accurate to
within ±0.5 °F (0.3 °C).
(b) If the interior arrangements of the unit under test do not
conform with those shown in Figure 5.2 of HRF-1-2008, the unit must
be tested by relocating the temperature sensors from the locations
specified in the figures to avoid interference with hardware or
components within the unit, in which case the specific locations
used for the temperature sensors shall be noted in the test data
records maintained by the manufacturer in accordance with 10 CFR
429.71, and the certification report shall indicate that
non-standard sensor locations were used. If any temperature sensor
is relocated by any amount from the location prescribed in Figure
5.2 of HRF-1-2008 in order to maintain a minimum 1-inch air space
from adjustable shelves or other components that could be relocated
by the consumer, except in cases in which the Figure prescribe a
temperature sensor location within 1 inch of a shelf or similar
feature, this constitutes a relocation of temperature sensors that
must be recorded in the test data and reported in the certification
report as described above.
5.1.1 Measured Temperature. The measured temperature is to be
the average of all sensor temperature readings taken at a
particular point in time. Measurements shall be taken at regular
intervals not to exceed 4 minutes.
5.1.2 Compartment Temperature. The compartment temperature for
each test period shall be an average of the measured temperatures
taken in a compartment during the test period as defined in section
4 of this appendix. For long-time automatic defrost models,
compartment temperature shall be that measured in the first part of
the test period specified in section 4.2.1 of this appendix. For
models with variable defrost controls, compartment temperature
shall be that measured in the first part of the test period
specified in section 4.2.2 of this appendix. For models with
automatic defrost that is neither long-time nor variable defrost,
the compartment temperature shall be an average of the measured
temperatures taken in a compartment during a stable period of
compressor operation that (a) includes no defrost cycles or events
associated with a defrost cycle, such as precooling or recovery,
(b) is no less than three hours in duration, and (c) includes two
or more whole compressor cycles. If the compressor does not cycle,
the stable period used for the temperature average shall be three
hours in duration.
5.1.3 Freezer Compartment Temperature. The freezer compartment
temperature shall be calculated as:
Where: F
is the total number of applicable freezer compartments, which
include the primary freezer compartment and any number of separate
auxiliary freezer compartments; TFi is the compartment temperature
of freezer compartment “i” determined in accordance with section
5.1.2 of this appendix; and VFi is the volume of freezer
compartment “i”.
5.2 Energy Measurements:
5.2.1 Per-Day Energy Consumption. The energy consumption in
kilowatt-hours per day for each test period shall be the energy
expended during the test period as specified in section 4 adjusted
to a 24-hour period. The adjustment shall be determined as
follows:
5.2.1.1 Nonautomatic and Automatic Defrost Models. The energy
consumption in kilowatt-hours per day shall be calculated
equivalent to:
ET = (EP × 1440 × K) / T Where: ET = test cycle energy expended in
kilowatt-hours per day; EP = energy expended in kilowatt-hours
during the test period; T = length of time of the test period in
minutes; 1440 = conversion factor to adjust to a 24-hour period in
minutes per day; and K = dimensionless correction factor of 0.7 for
chest freezers and 0.85 for upright freezers to adjust for average
household usage.
5.2.1.2 Long-time Automatic Defrost. If the two-part test method
is used, the energy consumption in kilowatt-hours per day shall be
calculated equivalent to:
ET = (1440 × K × EP1/T1) + (EP2−(EP1 × T2/T1)) × K × (12/CT) Where:
ET, 1440, and K are defined in section 5.2.1.1; EP1 = energy
expended in kilowatt-hours during the first part of the test; EP2 =
energy expended in kilowatt-hours during the second part of the
test; CT = defrost timer run time or compressor run time between
defrosts in hours required to cause it to go through a complete
cycle, rounded to the nearest tenth of an hour; 12 = conversion
factor to adjust for a 50 percent run time of the compressor in
hours per day; and T1 and T2 = length of time in minutes of the
first and second test parts respectively.
5.2.1.3 Variable Defrost Control. The energy consumption in
kilowatt-hours per day shall be calculated equivalent to:
ET = (1440 × K × EP1/T1) + (EP2−(EP1 × T2/T1)) × K × (12/CT),
Where: ET, 1440, and K are defined in section 5.2.1.1 and EP1, EP2,
T1, T2, and 12 are defined in section 5.2.1.2; CT = (CTL × CTM)/(F
× (CTM − CTL) + CTL); CTL = the shortest compressor run time
between defrosts used in the variable defrost control algorithm
(greater than or equal to 6 but less than or equal to 12 hours), or
the shortest compressor run time between defrosts observed for the
test (if it is shorter than the shortest run time used in the
control algorithm and is greater than 6 hours), or 6 hours (if the
shortest observed run time is less than 6 hours), in hours rounded
to the nearest tenth of an hour; CTM = maximum compressor run time
between defrosts in hours rounded to the nearest tenth of an hour
(greater than CTL but not more than 96 hours); F = ratio of per day
energy consumption in excess of the least energy and the maximum
difference in per-day energy consumption and is equal to 0.20.
For variable defrost models with no values for CTL and CTM in
the algorithm, the default values of 6 and 96 shall be used,
respectively.
5.3 Volume Measurements. (a) The unit's total refrigerated
volume, VT, shall be measured in accordance with HRF-1-2008
(incorporated by reference; see § 430.3), section 3.30 and sections
4.2 through 4.3. The measured volume shall include all spaces
within the insulated volume of each compartment except for the
volumes that must be deducted in accordance with section 4.2.2 of
HRF-1-2008, as provided in paragraph (b) of this section.
(b) The following component volumes shall not be included in the
compartment volume measurements: Icemaker compartment insulation,
fountain recess, dispenser insulation, and ice chute (if there is a
plug, cover, or cap over the chute per Figure 4-2 of HRF-1-2008).
The following component volumes shall be included in the
compartment volume measurements: Icemaker auger motor (if housed
inside the insulated space of the cabinet), icemaker kit, ice
storage bin, and ice chute (up to the dispenser flap, if there is
no plug, cover, or cap over the ice chute per Figure 4-3 of
HRF-1-2008).
(c) Total refrigerated volume is determined by physical
measurement of the test unit. Measurements and calculations used to
determine the total refrigerated volume shall be retained as part
of the test records underlying the certification of the basic model
in accordance with 10 CFR 429.71.
(d) Compartment classification shall be based on subdivision of
the refrigerated volume into zones separated from each other by
subdividing barriers: No evaluated compartment shall be a zone of a
larger compartment unless the zone is separated from the remainder
of the larger compartment by subdividing barriers; if there are no
such subdividing barriers within the larger compartment, the larger
compartment must be evaluated as a single compartment rather than
as multiple compartments. If the cabinet contains a movable
subdividing barrier, it must be placed as described in section 2.5
of this appendix.
(e) Freezer compartment volumes shall be calculated and recorded
to the nearest 0.01 cubic feet. Total refrigerated volume shall be
calculated and recorded to the nearest 0.1 cubic feet.
6. Calculation of Derived Results From Test Measurements
6.1 Adjusted Total Volume. The adjusted total volume of each
tested unit must be determined based upon the volume measured in
section 5.3 of this appendix using the following calculations.
Where volume measurements for the freezer are recorded in liters,
the measured volume must be converted to cubic feet and rounded to
the nearest 0.01 cubic foot prior to calculating the adjusted
volume. Adjusted total volume shall be calculated and recorded to
the nearest 0.1 cubic foot. The adjusted total volume, AV, for
freezers under test shall be defined as:
AV = VT × CF Where: VA = adjusted total volume in cubic feet; VT =
total refrigerated volume in cubic feet; and CF = dimensionless
correction factor of 1.76.
6.2 Average Per-Cycle Energy Consumption. The average per-cycle
energy consumption for a cycle type, E, is expressed in
kilowatt-hours per cycle to the nearest one hundredth (0.01)
kilowatt-hour, and shall be calculated according to the sections
below.
6.2.1 If the compartment temperature is always below 0.0 °F
(−17.8 °C), the average per-cycle energy consumption shall be
equivalent to:
E = ET1 + IET Where: E = total per-cycle energy consumption in
kilowatt-hours per day; ET is defined in section 5.2.1 of this
appendix; The number 1 indicates the test during which the highest
compartment temperature is measured; and IET, expressed in
kilowatt-hours per cycle, equals 0.23 for a product with an
automatic icemaker and otherwise equals 0 (zero).
6.2.2 If one of the compartment temperatures measured for a test
is greater than 0.0 °F (17.8 °C), the average per-cycle energy
consumption shall be equivalent to:
E = ET1 + ((ET2 − ET1) × (0.0 − TF1)/(TF2 − TF1)) + IET Where: E
and IET are defined in section 6.2.1 of this appendix and ET is
defined in section 5.2.1 of this appendix; TF = freezer compartment
temperature determined according to section 5.1.3 of this appendix
in degrees F; The numbers 1 and 2 indicate measurements taken
during the two tests to be used to calculate energy consumption, as
specified in section 3 of this appendix; and 0.0 = standardized
compartment temperature in degrees F.
6.2.3 Variable Anti-Sweat Heater Models. The standard cycle
energy consumption of a freezer with a variable anti-sweat heater
control (Estd), expressed in kilowatt-hours per day, shall be
calculated equivalent to:
Estd = E + (Correction Factor) where E is determined by 6.2.1, or
6.2.2, whichever is appropriate, with the anti-sweat heater switch
in the “off” position or, for a product without an anti-sweat
heater switch, the anti-sweat heater in its lowest energy use
state. Correction Factor = (Anti-sweat Heater Power × System-loss
Factor) × (24 hrs/1 day) × (1 kW/1000 W) Where: Anti-sweat Heater
Power = 0.034 * (Heater Watts at 5%RH) + 0.211 * (Heater Watts at
15%RH) + 0.204 * (Heater Watts at 25%RH) + 0.166 * (Heater Watts at
35%RH) + 0.126 * (Heater Watts at 45%RH) + 0.119 * (Heater Watts at
55%RH) + 0.069 * (Heater Watts at 65%RH) + 0.047 * (Heater Watts at
75%RH) + 0.008 * (Heater Watts at 85%RH) + 0.015 * (Heater Watts at
95%RH) Heater Watts at a specific relative humidity = the nominal
watts used by all heaters at that specific relative humidity, 72 °F
ambient (22.2 °C), and DOE reference freezer (FZ) average
temperature of 0 °F (−17.8 °C). System-loss Factor = 1.3 7. Test
Procedure Waivers
To the extent that the procedures contained in this appendix do
not provide a means for determining the energy consumption of a
basic model, a manufacturer must obtain a waiver under § 430.27 to
establish an acceptable test procedure for each such basic model.
Such instances could, for example, include situations where the
test set-up for a particular basic model is not clearly defined by
the provisions of section 2 of this appendix. For details regarding
the criteria and procedures for obtaining a waiver, please refer to
§ 430.27.
[75 FR 78866, Dec. 16, 2010, as amended at 76 FR 12502, Mar. 7,
2011; 76 FR 24781, May 2, 2011; 77 FR 3577, Jan. 25, 2012; 79 FR
22354, Apr. 21, 2014; 79 FR 41418, July 16, 2014; 81 FR 46803, July
18, 2016]