Title 46

SECTION 161.002-6

161.002-6 Testing requirements.

§ 161.002-6 Testing requirements.

(a) Devices must be tested and listed for fire service by an accepted independent laboratory, as accepted in accordance with § 159.010 of this subchapter, or by a NRTL as set forth in 29 CFR 1910.7.

(b) Each fire detection device must comply with the following standards (incorporated by reference, see § 161.002-1) as appropriate:

(1) Control units - UL 864;

(2) Heat detectors - UL 521;

(3) Smoke detectors - UL 268;

(4) Flame detectors - ANSI/FM 3260;

(5) Audible alarms - UL 464 or UL 1480;

(6) Visual alarms - UL 1971; and

(7) Manual Signaling Boxes - UL 38.

(c) All devices must be tested by an accepted independent laboratory, as defined in § 159.010 of this subchapter, to meet the marine environment testing requirements in Table 161.002-6(c) of this section. The test parameters are found in IEC 60092-504 (incorporated by reference, see § 161.002-1).

Table 161.002-6(c) - Marine Environmental Testing Requirements

IEC 60092-504 Environmental type test Category 1 Category 2 Category 3
All spaces not Category 2 or 3 Open deck or open to weather Spaces containing navigation or communication equipment
1 - Visual inspection X X X
2 - Functional test X X X
3 - High voltage test X X X
4a - Power supply variations X X X
4b - Power supply failure X X X
5 - Insulation resistance X X X
6 - Cold with gradual temp. change X (5 °C) X (−25 °C) X (5 °C)
7 - Dry heat with gradual temp. change X (55 °C) X (55 °C) X (55 °C)
8 - Damp heat, cyclic X X X
9 - Salt mist X
10 - Vibration (sinusoidal) X X X
11b - Inclination, dynamic 1 X 1 X 1 X
13 - Electrostatic discharge X X X
14 - Electromagnetic field X X X
15 - Conducted low frequency X X X
16(a) - Conducted radio frequency (3 V rms) X
16(b) - Conducted radio frequency (10 V rms) X X
17 - Burst/fast transients X X X
18 - Surge/slow transients X X X
19(a) - Radiated emission (general power) X
19(b) - Radiated emission (bridge and deck zone) X X
20(a) - Conducted emission (general power) X
20(b) - Conducted emission (bridge and deck zone) X X

1 This test only needs to be completed if the device is in a location with moving mechanical parts.

(d) All fire detection system control units and remote annunciators must have enclosure protection as outlined in part 5 of IEC 60092-504 (incorporated by reference, see § 161.002-1) if the requirements exceed those of 46 CFR 111.01-9. Otherwise, 46 CFR 111.01-9 must be complied with.

[USCG-2012-0196, 81 FR 48275, July 22, 2016]