Title 46

SECTION 108.445

108.445 Alarm and means of escape.

§ 108.445 Alarm and means of escape.

(a) Each CO2 system that has a supply of more than 136 kilograms (300 pounds) of CO2, except a system that protects a tank, must have an alarm that sounds for at least 20 seconds before the CO2 is released into the space.

(b) Each audible alarm for a CO2 system must have the CO2 supply for the system as its source of power and must be in a visible location in the spaces protected.