eCFR.io
Daily eCFR

§ 56.12028 Testing grounding systems.

30 CFR 56.12028

Citation30 CFR 56.12028
CorpusDaily eCFR
Displayed edition2026-09-21
Last updated2026-09-21

§ 56.12028 Testing grounding systems.

Continuity and resistance of grounding systems shall be tested immediately after installation, repair, and modification; and annually thereafter. A record of the resistance measured during the most recent tests shall be made available on a request by the Secretary or his duly authorized representative.